Free EPA 608 Practice Test (Core, Type I, II, III & Universal)
Select any module below to start immediately with zero registration. Switch between Study Mode (instant 40 CFR explanations) and Timed Exam Mode (official 25-question / 72% pass grading).
EPA Section 608 Interactive Exam Simulator
Switch between Core, Type I, Type II, Type III (25Q each), or launch the full 100-Question Universal Exam.
In which layer of the Earth’s atmosphere is the protective ozone layer primarily located?
0% (0 / 0)
Question-by-Question Review
Your Module Mastery Progress
Dedicated EPA 608 Section Practice Tests & Reference Tools
EPA 608 Core
Mandatory for all certifications: stratospheric ozone, Clean Air Act, 3 Rs, cylinders, safety, and vacuum fundamentals.
EPA 608 Type I (Small Appliances)
Factory-sealed appliances containing ≤5 lbs of refrigerant: 80%/90% recovery, passive vs active units, and A3 hydrocarbons.
EPA 608 Type II (High-Pressure)
Residential & commercial AC, heat pumps, refrigeration racks: 0/10/15 in. Hg evacuation, 10%/20%/30% leak thresholds, and A2Ls.
EPA 608 Type III (Low-Pressure)
Low-pressure centrifugal chillers (R-11/R-123/R-1233zd): 25 mm Hg absolute evacuation, 10 psig max test, purge units, freeze prevention.
Full 4-section simulation grading Core + Type I + II + III independently at 72%.
Interactive Refrigerant P/T Chart →Lookup R-410A, R-22, R-32, R-454B, R-134a, R-123 pressures, ODP, GWP & ASHRAE classes.
Evacuation Requirements Cheat Sheet →Interactive appliance selector + printable Before/After Nov 15, 1993 table.
Leak Repair Thresholds (10%/20%/30%) →Interactive annualized leak-rate calculator, 30-day repair & 125% chronic leaker rules.
A2L Refrigerants & AIM Act Guide →2025–2026 R-32 / R-454B transition, LH cylinder threads, and spark-free service tools.
EPA 608 Cost & Proctor Guide →Compare ESCO, SkillCat, Mainstream, and Ferris State exam fees and proctoring formats.
EPA 608 Required Evacuation Levels (40 CFR §82.156 Table 1)
Memorizing this single table guarantees 4 to 8 correct answers across Type I, Type II, and Type III.
| Appliance Type | EPA Type | Charge Size | Equip. Before Nov 15, 1993 | Equip. On/After Nov 15, 1993 |
|---|---|---|---|---|
| Small Appliances (Operating Compressor) | Type I | ≤ 5 lbs (factory sealed) | 80% or 4 in. Hg | 90% or 4 in. Hg |
| Small Appliances (Non-Operating Compressor) | Type I | ≤ 5 lbs (factory sealed) | 80% or 4 in. Hg | 80% or 4 in. Hg |
| HCFC-22 (R-22) Appliances | Type II | < 200 lbs | 0 in. Hg | 0 in. Hg |
| HCFC-22 (R-22) Appliances | Type II | ≥ 200 lbs | 4 in. Hg | 10 in. Hg |
| Other High-Pressure (R-410A, R-134a, R-404A, R-407C) | Type II | < 200 lbs | 4 in. Hg | 10 in. Hg |
| Other High-Pressure (R-410A, R-134a, R-404A, R-407C) | Type II | ≥ 200 lbs | 4 in. Hg | 15 in. Hg |
| Very High-Pressure (R-13, R-503) | Type II | Any size | 0 in. Hg | 0 in. Hg |
| Low-Pressure Centrifugal Chillers (R-11, R-123, R-514A) | Type III | Any size | 25 in. Hg | 25 mm Hg absolute |
EPA 608 Leak Repair Thresholds (Appliances ≥ 50 lbs)
| Sector | Trigger Leak Rate | Repair Deadline | Verification Tests |
|---|---|---|---|
| Comfort Cooling Office chillers, commercial building rooftop AC, heat pumps | 10% | 30 days | Initial (before recharge) + Follow-up within 10 days |
| Commercial Refrigeration Supermarket racks, walk-in cold storage warehouses, refrigerated transport | 20% | 30 days | Initial (before recharge) + Follow-up within 10 days |
| Industrial Process Refrigeration (IPR) Chemical, petrochemical, pharmaceutical, manufacturing process cooling | 30% | 30 days (120 days if industrial shutdown required) | Initial + Follow-up within 10 days |
| Chronically Leaking Appliance Report Any regulated ≥ 50 lb appliance leaking ≥ 125% of full charge in a calendar year | ≥ 125% / calendar year | EPA report due March 1 of following year | Documented repair / retrofit / retirement actions |
Top 6 EPA 608 Exam Traps That Trip Up Experienced Technicians
- Mixing up 25 in. Hg vs. 25 mm Hg absolute (Type III): Pre-Nov 15, 1993 recovery equipment uses 25 inches Hg; post-Nov 15, 1993 requires 25 mm Hg absolute (~29 in. Hg vacuum).
- Forgetting the 10 psig chiller pressure limit: Never exceed 10 psig when pressure-testing a low-pressure chiller because its safety rupture disc blows at 15 psig.
- Using old 15% / 35% leak thresholds: Modern 40 CFR §82.157 rules lowered leak repair triggers to 10% (comfort cooling), 20% (commercial refrigeration), and 30% (industrial process).
- Charging liquid R-123 into a deep vacuum: Always break a chiller vacuum with VAPOR first (with water pumps running) until saturation rises above 32°F before adding liquid, or evaporator tubes will freeze and split.
- Confusing Recycle vs. Reclaim: Recycled refrigerant can only go back to the same owner; reselling used refrigerant to a new owner legally requires EPA-certified Reclamation to AHRI Standard 700.
- Using R-22 evacuation values for R-410A/R-404A: R-22 under 200 lbs is 0 in. Hg, whereas other high-pressure refrigerants under 200 lbs require 10 in. Hg (and ≥200 lbs require 15 in. Hg).
EPA 608 Practice Test FAQ
What score do I need to pass the EPA 608 exam?
You must score at least 72% (18 correct out of 25 questions) on the Core section AND at least 72% on each Type section (Type I, Type II, or Type III) you wish to earn. Passing Core plus all three Types awards EPA 608 Universal certification.
How many questions are on the real EPA Section 608 Universal exam?
The official Universal exam consists of 100 multiple-choice questions divided into four 25-question sections: Core (25), Type I (25), Type II (25), and Type III (25). Most proctors allow 2 to 3 hours for all four sections.
Is this EPA 608 practice test free without registration?
Yes. All 130 original EPA 608 questions, Core/Type I/II/III/Universal timed simulators, interactive P/T & evacuation charts, and printable cheat sheets are 100% free with zero login. Progress and missed questions save locally in your browser.
Are AIM Act and A2L refrigerant (R-32, R-454B) updates included?
Yes. Our 130-question bank covers core 40 CFR Part 82 Subpart F standards (evacuation levels, 10%/20%/30% leak thresholds, 25 mm Hg absolute chillers) plus 2025–2026 AIM Act HFC phasedown and A2L safety rules.