DOC-EPA-608 · 40 CFR PART 82 SUBPART F · 130 QUESTIONS

Free EPA 608 Practice Test (Core, Type I, II, III & Universal)

Select any module below to start immediately with zero registration. Switch between Study Mode (instant 40 CFR explanations) and Timed Exam Mode (official 25-question / 72% pass grading).

EPA-608-SIM 25 Questions · 72% Pass Line

EPA Section 608 Interactive Exam Simulator

Switch between Core, Type I, Type II, Type III (25Q each), or launch the full 100-Question Universal Exam.

Q 1 / 25 Loading topic…
Score: 0/0

In which layer of the Earth’s atmosphere is the protective ozone layer primarily located?

Local Browser Study Tracker

Your Module Mastery Progress

Open Wrong-Answer Notebook & History →
Core 0%
0 / 35 mastered
Type I 0%
0 / 30 mastered
Type II 0%
0 / 35 mastered
Type III 0%
0 / 30 mastered

Dedicated EPA 608 Section Practice Tests & Reference Tools

EPA 608 Required Evacuation Levels (40 CFR §82.156 Table 1)

Memorizing this single table guarantees 4 to 8 correct answers across Type I, Type II, and Type III.

Appliance Type EPA Type Charge Size Equip. Before Nov 15, 1993 Equip. On/After Nov 15, 1993
Small Appliances (Operating Compressor) Type I ≤ 5 lbs (factory sealed) 80% or 4 in. Hg 90% or 4 in. Hg
Small Appliances (Non-Operating Compressor) Type I ≤ 5 lbs (factory sealed) 80% or 4 in. Hg 80% or 4 in. Hg
HCFC-22 (R-22) Appliances Type II < 200 lbs 0 in. Hg 0 in. Hg
HCFC-22 (R-22) Appliances Type II ≥ 200 lbs 4 in. Hg 10 in. Hg
Other High-Pressure (R-410A, R-134a, R-404A, R-407C) Type II < 200 lbs 4 in. Hg 10 in. Hg
Other High-Pressure (R-410A, R-134a, R-404A, R-407C) Type II ≥ 200 lbs 4 in. Hg 15 in. Hg
Very High-Pressure (R-13, R-503) Type II Any size 0 in. Hg 0 in. Hg
Low-Pressure Centrifugal Chillers (R-11, R-123, R-514A) Type III Any size 25 in. Hg 25 mm Hg absolute

EPA 608 Leak Repair Thresholds (Appliances ≥ 50 lbs)

Sector Trigger Leak Rate Repair Deadline Verification Tests
Comfort Cooling
Office chillers, commercial building rooftop AC, heat pumps
10% 30 days Initial (before recharge) + Follow-up within 10 days
Commercial Refrigeration
Supermarket racks, walk-in cold storage warehouses, refrigerated transport
20% 30 days Initial (before recharge) + Follow-up within 10 days
Industrial Process Refrigeration (IPR)
Chemical, petrochemical, pharmaceutical, manufacturing process cooling
30% 30 days (120 days if industrial shutdown required) Initial + Follow-up within 10 days
Chronically Leaking Appliance Report
Any regulated ≥ 50 lb appliance leaking ≥ 125% of full charge in a calendar year
≥ 125% / calendar year EPA report due March 1 of following year Documented repair / retrofit / retirement actions

Top 6 EPA 608 Exam Traps That Trip Up Experienced Technicians

EPA 608 Practice Test FAQ

What score do I need to pass the EPA 608 exam?

You must score at least 72% (18 correct out of 25 questions) on the Core section AND at least 72% on each Type section (Type I, Type II, or Type III) you wish to earn. Passing Core plus all three Types awards EPA 608 Universal certification.

How many questions are on the real EPA Section 608 Universal exam?

The official Universal exam consists of 100 multiple-choice questions divided into four 25-question sections: Core (25), Type I (25), Type II (25), and Type III (25). Most proctors allow 2 to 3 hours for all four sections.

Is this EPA 608 practice test free without registration?

Yes. All 130 original EPA 608 questions, Core/Type I/II/III/Universal timed simulators, interactive P/T & evacuation charts, and printable cheat sheets are 100% free with zero login. Progress and missed questions save locally in your browser.

Are AIM Act and A2L refrigerant (R-32, R-454B) updates included?

Yes. Our 130-question bank covers core 40 CFR Part 82 Subpart F standards (evacuation levels, 10%/20%/30% leak thresholds, 25 mm Hg absolute chillers) plus 2025–2026 AIM Act HFC phasedown and A2L safety rules.